Design, Construction and Testing of a Cold Store With Water-Cooled Chiller
dc.authorscopusid | 55958611200 | |
dc.contributor.author | Akdemir, Serap | |
dc.date.accessioned | 2022-05-11T14:07:22Z | |
dc.date.available | 2022-05-11T14:07:22Z | |
dc.date.issued | 2022 | |
dc.department | Meslek Yüksekokulları, Teknik Bilimler Meslek Yüksekokulu, Makine ve Metal Teknolojileri Bölümü | |
dc.description.abstract | Objective of this research was to de-sign, construction and test of a cold store with chiller unit. Dimensions of the cold store were 5x4x3m. Heat load was calculated and capacity of cooling system was determined. Ambient temperature was set 2°C and relative humidity 90% for cold store testing. Am-bient temperature, relative humidity and air velocity were measured for 3 different levels and 12 points for each level in the cold store. Total heat load and capac-ity of cooling system were calculated 6264 kcal/h (7.284 kW). The descriptive statistics were calculated for the ambient temperature; mean, 2.82°C, standard deviation 0.02°C and CV (%) 0.56, and for the rela-tive humidity; mean 88.01%, standard deviation 0.61 (%) and CV(%) 0.70 and for the air velocity mean 0.37m/s, standard deviation 0.22 m/s, CV 33.45 %. Even the air velocity CV was high, the ambient tem-perature and relative humidity variations were eval-uated very good © 2022, Latin American Applied Research. All Rights Reserved. | |
dc.identifier.doi | 10.52292/j.laar.2022.635 | |
dc.identifier.endpage | 26 | |
dc.identifier.issn | 0327-0793 | |
dc.identifier.issue | 1 | en_US |
dc.identifier.scopus | 2-s2.0-85123592929 | |
dc.identifier.scopusquality | Q3 | |
dc.identifier.startpage | 21 | |
dc.identifier.uri | https://doi.org/10.52292/j.laar.2022.635 | |
dc.identifier.uri | https://hdl.handle.net/20.500.11776/5085 | |
dc.identifier.volume | 52 | |
dc.identifier.wos | WOS:000739328900004 | |
dc.identifier.wosquality | Q4 | |
dc.indekslendigikaynak | Web of Science | |
dc.indekslendigikaynak | Scopus | |
dc.institutionauthor | Akdemir, Serap | |
dc.language.iso | en | |
dc.publisher | Plapiqui | |
dc.relation.ispartof | Latin American Applied Research | |
dc.relation.publicationcategory | Makale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı | en_US |
dc.rights | info:eu-repo/semantics/openAccess | |
dc.subject | Chiller | |
dc.subject | Cold store | |
dc.subject | Design | |
dc.subject | Heat load | |
dc.title | Design, Construction and Testing of a Cold Store With Water-Cooled Chiller | |
dc.type | Article |