Energy Consumption of An Experimental Cold Storage

dc.authorid0000-0001-5057-174X
dc.authorwosidAkdemir, Serap/W-3806-2017
dc.contributor.authorAkdemir, Serap
dc.date.accessioned2022-05-11T14:47:54Z
dc.date.available2022-05-11T14:47:54Z
dc.date.issued2012
dc.departmentMeslek Yüksekokulları, Teknik Bilimler Meslek Yüksekokulu, Makine ve Metal Teknolojileri Bölümü
dc.description.abstractEnergy consumption of an experimental cold storage Was measured for different storage temperatures. Suction temperature and pressure temperature of the compressor and working time of the compressor were determined to reach evaporator set up temperatures. Capacity of compressor, condenser, and evaporator were 10460 kJ/h, 12552 kJ/h, and 10460 kJ/h, respectively. An axial fan located back of the evaporator was used to distribute the cooled air into the cold store. An electrical heater was used to. defrost. Refrigerant was R22. The compressor suction and pressure temperatures varied between 1.8 degrees C-14 degrees C; and 37 degrees C-44 degrees C, respectively. Condenser output temperature changed from 28.8 to 45.5 degrees C. Electrical energy consumption were measured as 0.001 kWh for 5 degrees C, 4 degrees C, and 3 degrees C and 0.003 kWh for 2 degrees C, 0.006 kWh for 1 degrees C, 0.001 kWh for -1 degrees C, 0.109 kWh for -2 degrees C and 0.120 kWh for -3 degrees C. Mean energy consumption of the compressor was 0.035 kWh/degrees C for positive cold storage temperatures (from 5 degrees C to 0 degrees C) and 0.093 kWh/degrees C for negative temperatures (-1 degrees C, -2 degrees C, and -3 degrees C). Working tithe of the compressor was changed from 207 s to 25049 s for test temperatures.
dc.identifier.endpage996
dc.identifier.issn1310-0351
dc.identifier.issue6en_US
dc.identifier.scopus2-s2.0-84874922508
dc.identifier.scopusqualityQ3
dc.identifier.startpage991
dc.identifier.urihttps://hdl.handle.net/20.500.11776/10570
dc.identifier.volume18
dc.identifier.wosWOS:000326315300024
dc.identifier.wosqualityQ4
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.institutionauthorAkdemir, Serap
dc.language.isoen
dc.publisherScientific Issues Natl Centre Agrarian Sciences
dc.relation.ispartofBulgarian Journal of Agricultural Science
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.subjectenergy consumption
dc.subjectcold storage
dc.subjectrefrigeration
dc.titleEnergy Consumption of An Experimental Cold Storage
dc.typeArticle

Dosyalar

Orijinal paket
Listeleniyor 1 - 1 / 1
Küçük Resim Yok
İsim:
10570.pdf
Boyut:
267.85 KB
Biçim:
Adobe Portable Document Format
Açıklama:
Tam Metin / Full Text