Gelişmiş Arama

Basit öğe kaydını göster

dc.contributor.authorDoğan, Ahmet
dc.contributor.authorKayacı, Nurullah
dc.contributor.authorDemir, Hahan
dc.contributor.authorKemal Sevindir, M.
dc.date.accessioned2023-04-20T08:05:56Z
dc.date.available2023-04-20T08:05:56Z
dc.date.issued2022
dc.identifier.issn2148-7847
dc.identifier.urihttps://doi.org/10.18186/thermal.1149161
dc.identifier.urihttps://hdl.handle.net/20.500.11776/11112
dc.description.abstractThe number of radiant heating-cooling systems in building applications is increasing it is because of low energy consumption, low operating temperature and high values they provide in terms of working compatibility with renewable energy sources. In this study, ground source heat pump integrated radiant panels installed on the wall and suspended ceiling of the office room in Yıldız Technical University Science and Technology Application and Research Centre were experimentally examined in terms of thermal comfort according to the relevant standards. Vertical air temperature differences and mean radiant temperatures were investigated. The mean air temperature differences at 0.1 m and 1.7 m were found to be 3,9 oC 2.9 oC 3.5 oC, 3.1 oC and 3.4 oC on average for the five different stands, respectively. PMV and PPD values were found to be 0.78 and 18.9% for February 12 (Case 1), 0.36 and 8.4% for February 13 (Case 2), respectively. In the experiment carried out under the conditions of Case 2, while the comfort conditions were provided in almost all of the day, the desired comfort conditions could not be achieved in Case 1 after 11 am. © 2022. All Rights Reserved.en_US
dc.description.sponsorshipYildiz Teknik Üniversitesi: FBA-2019-3703en_US
dc.description.sponsorshipThis study was supported by Yıldız Technical University under BAP program with GRANT No. FBA-2019-3703. We would like to thank to the Yıldız Technical University for their financial support during this work.en_US
dc.language.isoengen_US
dc.publisherYildiz Technical Universityen_US
dc.identifier.doi10.18186/thermal.1149161
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectGSHPen_US
dc.subjectHeat Pumpen_US
dc.subjectRadiant Systemsen_US
dc.subjectThermal Comforten_US
dc.subjectWall and Ceiling Heatingen_US
dc.titleExperimental investigation of thermal comfort performance of a radiant wall and ceiling panel systemen_US
dc.typearticleen_US
dc.relation.ispartofJournal of Thermal Engineeringen_US
dc.departmentFakülteler, Çorlu Mühendislik Fakültesi, Makine Mühendisliği Bölümüen_US
dc.identifier.volume8en_US
dc.identifier.issue4en_US
dc.identifier.startpage551en_US
dc.identifier.endpage561en_US
dc.institutionauthorKayacı, Nurullah
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.authorscopusid57833380700
dc.authorscopusid55645106500
dc.authorscopusid36837521200
dc.authorscopusid56461338200
dc.identifier.scopus2-s2.0-85135515434en_US


Bu öğenin dosyaları:

Thumbnail

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster